Product : ISaGRAF V3
Date : 24-April-1996
File : PCscada.Implement a SCADA comm link on a PC target.htm
Subject : How to implement a SCADA comm link on a PC target
Keywords: SCADA - Communication link
____________________________________________________________________
Below are main features which have to be developped to implement
a communication link between a PC ISaGRAF target (mono-task) and
a scada system:
1- Install a comm driver
2- In dba_init entry point (from server in synchronous mode)
make a pulling system to get request from the communication
3- Use BF_BOO and BF_ANA arrays to read variable values from
ISaGRAF database. Other services from server option in
synchronous mode can also be used to read/write variables.
Such a development has to be independent from the development of
IO drivers and C function blocks.
You have to ensure that the comm driver you use can be used with
the ISaGRAF one. If not, you have to use the IDK (ISaGRAF Development
Kit) to redirect both ISaGRAF standard communication and SCADA link to
a multi-port comm driver.
____________________________________________________________________
Remember it is also possible to replace the debugger by the
SCADA if both communications do not need to run simultaneously
and if the SCADA protocol is MODBUS.
____________________________________________________________________